Silicone Rubber Extruded Fiberglass Sleeving

High Voltage Sleeving for Demanding Applications


SFAG.06WH
Qty:  

What's special about this extruded fiberglass sleeving?

  • NEMA: TF-1, Type 5 Thermal: Thermal Class 200°C
  • Rated Class H by IEEE standards
  • Acceptable for continuous service from -70°C through 200°C. Operation at temperatures up to 315°C is tolerated for short durations.
  • Exceeds the requirements of UL Subject 224 for 200°C, 600-volt operation
  • Exceeds the requirements of MIL-I-3190/6, MIL-P-18057 (grade A), and ASTM D372
  • Click for More Features
  •  
  • RoHS Compliant

High Voltage Silicone Rubber Extruded Fiberglass Sleeving has many uses and is recommended for the insulation of leads and connections in electrical and electronic components (transformers, coils, relays, solenoids etc.) where temperature extremes from -70°C through 200°C are encountered. It's made with a combination of silicone and rubber extruded onto a braided fiberglass sleeving.

"A" Grade

Part # AWG Size Min. Diameter Max. Diameter Spool Size Color Price
SFAG.06WH 6 0.166" 0.178" 250' White
Qty:  
Manufacturer Direct

The silicone rubber coated sleeving is the only flexible insulating material appropriate for continuous service in ambient temperatures from -70°C through +200°C.

  1. NEMA: TF-1, Type 5 Thermal: Thermal Class 200°C
  2. Rated Class H by IEEE standards
  3. Acceptable for continuous service from -70°C through 200°C. Operation at temperatures up to 315°C is tolerated for short durations.
  4. Exceeds the requirements of UL Subject 224 for 200°C, 600-volt operation
  5. Exceeds the requirements of MIL-I-3190/6, MIL-P-18057 (grade A), and ASTM D372
  6. Environmental:
    1. Resistant to moisture, corona, ozone, radiation, compression set, fungus, most chemicals and solvents, weathering, flexure fatigue and heat degradation.
  7. Flammability:
    1. Slow-burn.
    2. The coating maintains its electrical integrity even under severe fire conditions by forming a non-conductive ash.
  8. Compliant with the European Union's Restrictions on the use of Hazardous Substances (RoHS) Directive

 

Part # Dielectric Grade Min. Ave. Breakdown Min. Indiv
SPSILA A 7000 6000

View Measurement Conversion Chart

Manuals

 

Related Articles



 

How-To Corner




 

Request A Quote

Did you know that we can give you a quote for most of our products, including shipping?

You can also call us toll free 1-833-3CABLEORG (1-833-322-2536)

Questions & Answers

Do you have any questions about this product?
Let our experts and customers resolve all your doubts