Sample specifications are provided under separate cover. CAUTION: firestopping is ideally specified under Section 07270, as a separate work scope tendered by specialty, 3M trained, applicators to the general contractors. Specifiers are advised to instruct the chief designer to provide clear identification of wall ratings in the form of overlays on separate drawings.
Related Sections of Work are:
03300 Concrete Form work
04200 Unit Masonry
07900 Joint Sealers
05300 Metal Decking
07250 Spray Applied Fireproofing
08900 Glazed Curtain Wall
09100 Metal Support Systems
09250 Gypsum Board
15250 Basic Mechanical Materials& Methods
15250 Mechanical Insulation
15300 Fire Protection
15400 Plumbing
15500 HVAC
15550 Heat Generation
15650 Refrigeration
16050 Basic Electrical Materials & Methods
Specifiers are advised to search these sections for overlaps, in order to avoid problems that will otherwise appear at tender time and during execution.
Refer to CSC TEK-AID Section 07270 Firestopping, Master Specification for comprehensive firestop specification.
Physical Properties
| Appearance: |
solid powder with white particles and plastic fibers |
| Bulk Powder Density: |
37-57 lb/ft 3or 600-910 kg/m3 range between loose and compacted powders |
| Wet Densities: |
68-119 lb/ft 3 or 1,100-1,900 kg/m 3depending on water/powder ratio and placement methods |
| Cured Densities: |
43-87 lb/ft 3 700-1,400 kg/m3 depending on water to powder ratio and placement methods |
| Compression Strengths: |
187-790 PSI or 1.3-5.45 N/mm 2 depending on water to powder ratio and placement methods |
Performance
Tested per ASTM E814 and CAN/ULC-S115 for up to 2 hour fire resistance, F and T (F, FT, FH and FTH)
Listed for use in openings as follows: Electrical:
- 3’ x 6” (91 cm x 15 cm) cable trays, aluminum or steel
- 1C1000MCM full cabling of 3’ (91 cm) trays
- 45% actual (100% visual) cabling (power, instrumentation, communication)
- Bus Duct: up to 111.3 in2 or 21” x 5.3” (0.07m2 or 53.3 cm x 13.5 cm), 4500A copper, 3400A aluminum bars
Mechanical:
- 3” (76 mm) copper DWV/L or sched. 10S or heavier steel piping
- 1” to 6” (2.5 cm to 15 cm) pipe covering made of rock wool, calcium silicate or perlite
- ASJ, 0.01” (0.25 mm) stainless steel or 0.016” (0.41 mm) aluminum jacketing
- Tested with 8” (20 cm) steel piping + 6” (15 cm) pipe covering + 20” (51 cm) diameter penetrants
General:
- 22.7 ft² (2.11 m²) openings
- 280 lb (127 kg) concrete block loading test – passed
- Can be re-entered (re-entry and resealing performed on specimen prior to fire testing)
- “soft spots” made of Temperlite™ (by Knauf Fiber Glas GmbH) insulation sized 4” x 4” x 5” (10 cm x 10 cm x 12.5 cm)
- “slip-covers” consisting of 1/8” (3.2 mm) ceramic paper held on with ordinary duct tape and embedded in 3M Fire Barrier Mortar

FILL, VOID OR CAVITY MATERIALS FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS.
SEE UL DIRECTORY OF PRODUCTS CERTIFIED FOR CANADA AND UL FIRE RESISTANCE DIRECTORY 50L6. |