Home > Fire Protection > Fire Barrier Duct Wrap 15A
3M™ Fire Barrier Duct Wrap 15A
Better Fire Protection for Air Ventilation, Kitchen Grease Ducts, and Chemical Exhaust Ducts at a Fraction of the Installation Effort
Fire Barrier Duct Wrap |
What's special about this duct wrap?
|
3M™ Fire Barrier Duct Wrap 15A is a fire resistant wrap consisting of a patented inorganic blanket encapsulated with a scrim-reinforced foil. It is used to fire rate commercial kitchen grease ducts and is a proven alternative to 1 or 2 hour fire resistant rated shaft enclosures. This non-asbestos wrap contains a safer fiber construction and installs easily because of its high flexibility and strength.
3M™ Fire Barrier Duct Wrap 15A is the thinnest standard, single layer fire resistant wrap that has passed the UL1978 test which simulates a grease duct fire. With its excellent insulating capabilities, it is an ideal choice for tight spaces because it protects combustible constructions at zero clearance to the overlap or collar. 3M Fire Barrier 1000 N/S, 1003 S/L and 2000+ Silicone Sealants used in combination 3M™ Fire Barrier Duct Wrap 15A provide an effective firestop when the duct penetrates fire rated walls and floors.
- Thinnest, standard one layer wrap for grease ducts rated as a shaft alternative per UL 1978.
- Passes the rigors of internal grease duct fire tests UL 1978 and AC 101.
To view Installation Techniques, click here
- Thinnest, standard one layer wrap for grease ducts rated as a shaft alternative per UL 1978
- Zero clearance to the overlap or collar for congested spaces
- High flexibility for installation ease
- Foil encapsulated with unique center overlap seam for blanket protection, less dust, and high wrap strength
- Widest range of penetration seal systems
- Safer fiber construction
Applications
3M™ Fire Barrier Duct Wrap 15A is an ideal fire resistive enclosure for commercial kitchen grease ducts. It is a proven performance alternative to a 1 or 2 hour fire resistant rated shaft enclosures and provides zero clearance to combustible construction at overlap or collar. 3M™ Fire Barrier 1000 N/S, 1003 S/L or 2000+ Silicone Sealant is used in combination with 3M Fire Barrier Duct Wrap 15A to firestop the duct when the duct penetrates fire rated floors and walls.
Performance
3M Fire Barrier Duct Wrap 15A has been tested in accordance with the following:
ASTM C 411 ASTM E 119
ASTM C 518 ASTM E 136
ASTM E 84 ASTM E 814
UL 1978 (Sections 12 & 13)
Surface Burning Characteristics (ASTM E 84)
Foil Encapsulated Blanket:
Flame Spread: 0
Smoke Developed: 0
Blanket:
Flame Spread: 0
Smoke Developed: 0
Thermal Conductivity
| Temperature °F (°C) | btu•in. /(hr.•ft 2•F) |
| 500 (260) | 0.417 |
| 1000 (537) | 0.922 |
| 1500 (815) | 1.69 |
| 1800 (982) | 2.27 |
Grease Duct Listings
| Fire Resistive Rating | Enclosure System | Omega Point Lab. Design Nos. | |
| Duct System | Through-Penetration System | ||
| 1 or 2 hours | 1 layer of 3M Fire Barrier Duct Wrap 15A , 3 in. (76 mm) perimeter and longitudinal overlaps |
GD 532 F GD 538 F |
FS 557 W FS 558 F FS 559 W FS 560 F FS 561 F FS 562 W FS 563 W FS 578 F FS 579 W |
Code Compliance
3M Fire Barrier Duct Wrap 15A complies with
requirements of the following codes:
- BOCA ES Compliance Report 2161
- NFPA 96, 1998 Edition
- Standard Mechanical Code
- International Mechanical Code
- Standard Building Code
- SBCCI ES Compliance Report 2132
This is only a partial list of code compliance.
Please Note: There is a 5 Day Lead Time on all Duct Wrap orders.
| PART # | PACKAGE SIZE | WEIGHT | PRICE |
| FP-3M-FBD-24 | 1.5 in. x 24 in. x 20 ft. Roll | 53 lbs. | $295.00![]() |
| FP-3M-FBD-48 | 1.5 in. x 48 in. x 20 ft. Roll | 112 lbs. | $550.00![]() |
| To view Installation Techniques, click here | |||
To view Installation Techniques, click here
Warranty and Limited Remedy
Warranty and Limited Remedy
This product will be free from defects in material and manufacture for a period of ninety (90) days from date of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
User is responsible for determining whether the 3M product is fit for a particular purpose and suitable for user’s method of application. If this 3M product is proved to be defective within the warranty period stated above, your exclusive remedy and 3M’s sole obligation shall be, at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product.
Limitation of Liability
Except where prohibited by law, 3M will not be liable for any loss or damage arising from the use of this 3M product, whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including warranty, contract, negligence or strict liability.
RELATED ARTICLES -
- Which Firestop Product Should I Use for My Application?
- CableOrganizer.com’s Top 10 Products for Fire Protection
- How to Fireproof Your Server Room
- History of 3M Corporation
CATALOG - PDF
For your convenience, we have made our brochure and catalogs available online in PDF format. Downloading the PDF catalog will take you no more than 5 minutes, so you won’t have to wait days for the print catalog. PDF catalogs include links to our products: just click on the hyperlinked product headings, and you’ll be directed right to our website.
Office
PDF Catalog 2 MB
Automotive
PDF Catalog 2.6 MB
Aerospace/Aircraft
PDF Catalog 2 MB
Utilities & Energy
PDF Catalog 3.7 MB
Datacom/Telecom
PDF Catalog 5.7 MB






View Cart