The firestopping foam will be a two-part, silicone elastomer. The foam shall be listed by independent test agencies such as UL or FM and be tested to, and pass the criteria of, ASTM E 814 Fire Test, tested under positive pressure. It shall comply with the requirements of the NEC (NFPA70), BOCAI, ICBO, SBCCI and NFPA Code #101.
| Typically Specified Divisions |
Division 7
07270 |
Thermal and Moisture Protection Firestopping |
Division 13
13900 |
Special Construction Fire Suppression and Supervisory Systems |
Division 15
15250
15300
|
Mechanical
Mechanical Insulation Fire Protection |
Division 16
16050 |
Electrical
Basic Electrical Materials and Methods |
| Performance |
| Typical Physical Properties |
CTM 0176 |
Appearance........................................................Dark gray to black elastomeric foam |
CTM 092A
CTM 0845A
CTM 0826 |
Snap Time 2minutes........................................1 to 2
Density 3, lbs/ ft 3...............................................18 to 25
Cell Structure4
closed cell, percent
.........................................>50 |
ASTM D 3574
CTM 0740 |
Tensile Strength, psi
........................................15
K Factor 5, 17 lbs/cu ft foam,
BTU-in/hr-ft 2- °C
...............................................0.45 |
CTM 0585 |
Linear Coefficient of Thermal Expansion,
(-25 to 150 °C), cm/cm °C
...............................3.2 x 10 |
|
|
As Cured - Flammability 6 |
CTM 0316A |
Fixed Ignition Time, seconds ...........................20
Glow-Out Time, seconds...................................10 |
CTM 0780 |
Limiting Oxygen Index, LOI rating ....................39 |
1 One part A thoroughly mixed with one part B and cured at 25°C (77`F) for 24 hours.
2 Time to non-pour conditions. Also time to begin foam rise.
3 Power mixed for 30 seconds and cured in nonconfined condition.
4 Breathability method.
5 Cured foam sample thickness - -1.0 inch.
6 Tests, claims, representatives and descriptions regarding flammability are based on small-scale laboratory tests. Such tests are not reliable for determining, evaluation, predicting or describing the flammability or burning characteristics of the product under actual fire conditions, whether the product is used alone or in combination with other products.
B. Firestopping Properties
Meets the criteria of ASTM E 814 Fire Test, tested under positive pressure. Consult current UL Fire Resistance Directory for systems listed under 3M Product 2001 Silicone RTV Foam
C. Firestopping Code Requirements
ICBO Uniform
Building Code (1991 Edition) |
SBCCI Standard
Building Code (1991 Edition) |
BOCA Basic/National Building Code(1990 Edition) |
NFPA Life SafetyCode 101 (1991Edition) |
NEC National Electric Code |
CABO Council of American Building Officials Report Number |
302(d) Application for Permit
1704 Vertical Fire Spread st Exterior Walls
1706 Shaft Enclosure
1701 Construction Joints
4304(e) Walls and Partitions
4304(f) Membranes
4305 Floor/ Ceilings, Floors
|
103.2.4 Structural and Fire Resistance Integrity
705.1.6 Fire Stopping
1001.3 Penetrations of Fire Resistant Assemblies
1001.3.6 Method E: Through-Penetration Protection Systems
|
901.2 Penetrations
902.1 Structural Building Assemblies
913.4.1 Through-Penetration System (Floor/Ceiling, Roof/Ceiling Assemblies)
915.6 Vertical Shafts
|
6-2.3.6 Penetrations and Misc. Openings and Fire Barriers |
300-21 Fire Stopping |
NER 243 |

FILL, VOID OR CAVITY MATERIALS FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS.
SEE UL DIRECTORY OF PRODUCTS CERTIFIED FOR CANADA AND UL FIRE RESISTANCE DIRECTORY 50L6.